Q: Is our Copper Tape Shield (CTS) considered TC-ER?

A: Copper Tape Shield (CTS) is considered metallic shielding for our E8 / UL1072 (MV-105) cables. TC-ER is a UL listing for Tray Cables that have passed the additional "ER testing" for impact and crush resistance, usually attached to our PLTC/ITC, low voltage instrumentation, control and power cables (E1, E2 and E3). LS does not have a specific TC-ER UL listed cable that uses CTS. Many of our larger E8 cables can be used for tray cables (CT USE). TC-ER does not apply to CTS cables but the CTS cables 1/0AWG and larger can be installed in cable trays.

For example:

By LS Engineering October 24, 2024
Q: What is the difference between 1350 Aluminum and 8000 Series Aluminum Alloy?
By LS Engineering October 24, 2024
Q: What kind of material is used for strand filler in your filled strand primary cable? Is it a powder, gel or something different? Is the same strand material for all sizes and both copper and aluminum?
By LS Engineering March 28, 2024
Q: Where do I find standard reel sizes and protective coverings? How do I specify a specific reel size? What is the difference between CL1, CL2 and CL3 wooden reels?
By LS Engineering March 28, 2024
Q: Can LS manufacture MV URD EPR with an XLPE jacket?
By LS Engineering September 22, 2023
Q: Is LS MV-105 cable UL Listed or only UL Compliant?
By LS Engineering September 21, 2023
Q: Does LS offer low smoke, zero halogen (LSZH) cables?
By LS Engineering September 21, 2023
Q: Do we have a cross reference for LS LV tray cables and Belden?
By LS Engineering September 15, 2023
Q: Is your MV-105 with PVC jacket flame retardant?
By LS Engineering September 14, 2023
Q: Can we offer a 15kV 750MCM AIA three conductor with a 4/0 ground?
By LS Engineering September 14, 2023
Q: How can I tell if a part number / product description listed in the Inventory look up on the sales portal is for a standard product?